Fire Barriers and Ventilated Facade Fire Requirements

Fire barriers in a ventilated facade are steel elements that close off the air gap between the insulation and the cladding around window and door openings and, in some systems, at every floor. Their job is to stop flames from a burning room getting into the ventilation gap and spreading up the facade as if through a chimney.

The key criterion is that fire barriers must match the album of technical solutions of a system that has passed fire tests: material, thickness, projection, fixing spacing and locations are not chosen by eye. The topic matters to designers, technical supervisors and general contractors, as well as to clients who will go through design review and commissioning.

The general construction of rainscreen facades is in the Ventilated rainscreen facades section.

Requirements for rainscreen facades

The fire safety of a rainscreen facade system is determined for the construction as a whole, not for individual materials. The main requirements in Russia are set by Federal Law No. 123-FZ "Technical Regulations on Fire Safety Requirements" and the applicable codes of practice for fire protection.

• The fire hazard class of the external wall with a rainscreen facade must match the building's structural fire hazard class. Most multi-storey residential and public buildings require K0 — a non-fire-hazardous construction.

• Confirmation by testing. The class is determined by fire tests on a full-scale facade mock-up with an opening under Russian standard GOST 31251. The result applies only to the tested configuration: the same cladding, insulation, membrane, substructure and fire barriers.

• Insulation in a rainscreen facade is non-combustible.

• Cladding and membrane must have fire properties permissible for the given system and building class.

• Fire barriers and opening surrounds follow the album of technical solutions.

Requirements depend on building height, use and fire resistance degree, so for a specific project they are set in the design and checked in the design review.

Fire barriers

Fire barriers are the main structural element that interrupts the path of fire in the ventilation gap.

• Material. Galvanised or stainless steel of the thickness specified in the system album. Aluminium is not used for fire barriers: it melts at fire temperatures.

• Locations. Above window openings and around their perimeter — mandatory; horizontal barriers at every floor — if required by the system or design. On high-rise and complex buildings, vertical barriers are added at internal corners.

• Construction. The profile closes the ventilation gap fully or with perforation that allows air movement in normal operation but stops flame. A steel box surround is formed at the opening: reveals, sill and head element.

• Fixing. To the substrate with steel anchors, at the spacing given in the album. Fixing a barrier to an aluminium substructure does not replace fixing to the wall.

Fire barriers are installed together with the insulation and accepted with a concealed works record: once cladding is on, they cannot be seen.

Steel fire barrier above a window in a ventilated facade
Steel fire barrier above a window in a ventilated facade

K0 class materials

The fire hazard class of a facade is the class of the external wall construction with the rainscreen system, under the Russian classification: K0 (non-fire-hazardous), K1 (low fire hazard), K2 (moderate fire hazard), K3 (fire hazardous). The class is determined by tests based on how the mock-up behaves: presence of burning, damage to materials, heat effect.

ElementTypical requirement for K0 class systems
CladdingNon-combustible materials (e.g. GFRC of the NG group, porcelain stoneware, stone) or materials confirmed by testing as part of the system
InsulationNon-combustible mineral wool
Wind barrierNon-combustible or approved by system tests
SubstructureSteel or aluminium as tested; in high-rise buildings — steel elements at openings
Fire barriers and opening surroundsSteel, per the album of technical solutions

A non-combustible cladding material makes the task easier, but it is the system that gets the K0 class, not the panel. According to the company, the GFRC produced by TECHNOFORMA belongs to the NG (non-combustible) group.

Documents

Design review, technical supervision and acceptance require a set of documents:

• technical certificate for the facade system stating its scope of application;

• album of technical solutions with fire barrier and opening surround details;

• a conclusion on the system's fire hazard class based on fire tests;

• certificates or test reports on the combustibility of the cladding, insulation and membrane;

• the fire safety section of the design;

• concealed works records for the installation of fire barriers and insulation.

All documents must relate to the same system. A common mistake is cladding from one manufacturer, substructure from another and insulation from a third, with no tests for that combination.

Inspection

Technical supervision checks the fire safety of the rainscreen facade at every stage:

• before work begins — conformity of the design and materials with the system documents;

• during insulation — insulation and membrane brands against delivery notes and markings;

• during fire barrier installation — material, thickness, locations, fixing to the substrate, closure of the ventilation gap;

• during cladding — integrity of fire barriers, no combustible inserts, correct opening surrounds;

• at acceptance — completeness of concealed works records and photographs.

Typical violations: barriers above only some windows, aluminium instead of steel, barriers fixed to rails without anchoring into the wall, barriers missing at balcony doors.

Design changes during construction need particular attention. Replacing the cladding with a cheaper one, a different insulation, a different barrier spacing or a new opening shape may take the system outside the tested configuration. Any such change should be agreed with the designer and checked against the technical certificate before materials are bought, not after installation. Junctions with curtain walls, entrance groups and ventilation grilles are also checked: barriers are often interrupted at these points.

In service, fire barriers need no maintenance, but their integrity must be restored when the cladding is repaired or windows are replaced. If the facade is partly dismantled, before the panels are rehung it is checked that the opening surrounds and steel elements are in place and fixed to the substrate.

Window opening surround in a rainscreen facade system
Window opening surround in a rainscreen facade system

Examples from TECHNOFORMA projects

GFRC of the NG group is the main cladding material in TECHNOFORMA projects. An example of a public building is Chechen State University in Grozny: 4 storeys, 12,000 m² of GFRC, design and installation supervision in 2025. For large multi-storey projects — the Alye Parusa residential complex in Dagestan: 12 storeys, 4 buildings, 20,000 m² of GFRC, design and installation supervision 2018–2021.

Which documents confirm the system is described in "Technical certificate and technical assessment for a ventilated facade system".

FAQ

Where are fire barriers installed in a ventilated facade?

Mandatorily above and around window and door openings; at every floor and at corners — if required by the system or design.

What are fire barriers made of?

Galvanised or stainless steel of the thickness given in the album of technical solutions. Aluminium is not used.

What does K0 class mean for a facade?

A non-fire-hazardous construction under the Russian classification: in fire tests of a mock-up there is no fire spread and no unacceptable damage. The class is confirmed for the system as a whole.

Does non-combustible cladding guarantee the fire safety of a rainscreen facade?

No. Non-combustible insulation, an approved membrane, fire barriers and confirmation of the system by testing are also needed.

Who checks the fire safety of a rainscreen facade?

The design review, the client's technical supervision during installation and the regulatory authorities at commissioning.

Related articles

All articles
Ventilated Rainscreen Facade: Structure and How It Works

Ventilated rainscreen facades

Ventilated Rainscreen Facade: Structure and How It Works

A ventilated rainscreen facade is an external cladding system in which the finishing material is fixed to the wall via a metal substructure, set away from the insulation. A ventilated air gap remains between the insulation and the cladding, through which moisture escapes from the wall and insulation. Cladding options include porcelain stoneware, glass fibre reinforced concrete (GFRC), natural stone, fibre cement and metal panels.The main criterion for choosing a system is that the substructure, insulation and cladding are compatible with each other and meet the fire safety and load requirements for the particular building. Rainscreen facades are used on multi-storey residential buildings, office and public buildings, in refurbishment, and on private houses. All articles on the topic are in the section Ventilated rainscreen facades.

Rainscreen Substructures: Aluminium, Galvanised and Stainless Steel

Ventilated rainscreen facades

Rainscreen Substructures: Aluminium, Galvanised and Stainless Steel

A rainscreen substructure is a metal framework fixed to the load-bearing wall that holds the cladding away from the insulation, forming the ventilated gap. It consists of brackets, rails, anchors and cladding fixings and is made of aluminium alloys, coated galvanised steel or stainless steel.The main selection criterion is calculation: the substructure must carry the weight of the cladding and the wind load of the particular building with a margin, must not corrode in service, and must have confirmed compliance with the requirements for facade systems. The choice depends on the cladding, building height, climate and substrate. All articles on the topic are in the section Ventilated rainscreen facades.

Ventilated Rainscreen Facade Clad in GFRC

Ventilated rainscreen facades

Ventilated Rainscreen Facade Clad in GFRC

A GFRC (glass fibre reinforced concrete) ventilated facade is a rainscreen system in which the cladding consists of thin-walled panels and architectural elements made of GFRC, fixed to a metal substructure with an air gap over the insulation. The material is chosen when a facade needs plasticity — cornices, pilasters, window surrounds, rusticated surfaces, large relief panels — while the cladding must remain non-combustible and relatively light.The key selection criterion is not the panel itself but the combination of panel, cast-in fixings and substructure, engineered for a specific building. The solution suits residential complexes, hotels, public and office buildings where the architect works with a classical or neoclassical order or with a sculptural contemporary form.General principles of rainscreen systems are covered in the Ventilated rainscreen facades section; this article focuses on what sets GFRC apart.

Technical Certificate and Technical Assessment for a Ventilated Facade System

Ventilated rainscreen facades

Technical Certificate and Technical Assessment for a Ventilated Facade System

A technical certificate for a facade system is a federal-level document confirming that a ventilated rainscreen system is fit for use in construction in Russia. It is issued not for an individual bracket or panel but for the system as a whole: substructure, cladding, insulation, membrane, fasteners and details described in the album of technical solutions. Alongside the term "technical certificate" (TS), the industry uses the notion of a technical assessment of fitness (TO) — check the current form of the document and the procedure for obtaining it in official sources of the Russian Ministry of Construction.The key criterion is that the facade on site must match what is described in the certificate and album: materials, details and scope of application. This topic matters to designers, reviewers, technical supervisors and clients who want to avoid comments during design review and commissioning.Context is in the Ventilated rainscreen facades section.

Request a callback